Gasketed plate heat exchanger Condenser for Condensing applications
Baode Cond GPHE is a plate surface condenser designed for condensation under vacuum. Baode Condenser GPHE is based on semi-welded technology. Vapor condenses in the welded channel while the cooling medium passes through the gasketed channel. In addition to stainless steel, the plates are also available in titanium, which makes it possible to use seawater as a cooling medium.
Flow principle
Applications
• Biotech and Pharmaceutical
• Chemicals
• Energy and Utilities
• Food and Beverages
• Marine and Transportation
• Mining, Minerals and Pigments
• Pulp and Paper
• Water and Waste treatment
Benefits
• Optional sub-cooling of condensate and non-condensable gases
• Flexible configuration – heat transfer area can be modified
• Easy to install – compact design
• High serviceability – easy to open for inspection and cleaning
Features
Every detail is carefully designed to ensure optimal performance, maximum uptime and easy maintenance.
Selection of available features, depending on configuration some features may not be applicable:
• Reinforced hanger
• Glued gasket
• Fixed bolt head
• Lifting lug
• Lining
• Lock washer
• Tightening bolt cover
Working principle
Baode GPHE condenser is tailored for vacuum condensation. The large vapor inlet connection is placed centrally on the top and the smaller condensate outlet on each side in the bottom. The two medium sized connections for cooling media are centrally placed in the middle, which gives it a symmetrical design.
It uses the cassette concept with the plates welded in pairs. The vapor is condensed in the welded channel while plate pattern is specifically designed for optimal condensation, with an asymmetric channel configuration that features a large gap on the vapor side and the small gap on the colling water side. This make it possible to maintain a very low pressure drop on the vapor side while still keeping up the velocity and turbulence on the cooling water side, thus maximizing the heat transfer efficiency and minimizing fouling.
Dimensional drawing
Measurements mm (inches)
Model |
A |
B |
C |
D |
E |
F |
G |
AC400-W |
617 |
2217 |
1658 |
1215 |
457 |
236 |
270 |
AC600-W |
888 |
2860 |
2085 |
1470 |
657 |
393 |
455 |
Technical Data |
||
Plates |
Type |
Free channel, mm (in) |
AC400-W |
Semi-welded |
11/3 (0.43/0.12) |
AC600-W |
Semi-welded |
11/3 (0.43/0.12) |
Materials | ||
Heat transfer plates |
304/316L Stainless |
|
Field gaskets |
NBR, EPDM, FKM |
|
Ring gaskets |
NBR, EPDM, FKM |
|
Flange connections |
Metal lined, stainless steel |
|
Frame and pressure plates |
Carbon steel epoxy painted |
|
Operation Data |
|
|
Model |
Max. design pressure (bar/psig) |
Max. design temperature (°C/°F) |
AC400-W |
10 bar / 145psi |
160 °C / 320°F |
AC600-W |
10 bar / 145psi |
160 °C / 320°F |